Drainage pan for water heaters: The current UPC requires “Where a water heater is located in an attic, in or on an attic ceiling assembly, floor-ceiling assembly, floor-subfloor assembly or where damage results from a leaking water heater, a watertight pan of corrosion-resistant materials shall be installed beneath the water heater…” A proposal was considered to provide specific thickness requirements for the drain pans and flame spread index requirements for plastic drain pans. The proposal was provided with no substantiation for the thickness dimensions, and there is concern the ASTM flame spread index standard referenced is not appropriate. The Technical Committee did approve the proposal by majority vote, however, it did not receive the required 2/3 affirmative vote that will be needed in the letter ballot process. This proposal was also considered under the UMC.